building. climate. excellence.
building. climate. excellence.
The Vacumat Basic is a vacuum degasser for sealed heating (acc. to EN12828) and chilled water (cooling) installations that uses vacuum degassing technology for highly efficient degassing of closed systems. Moreover, the Vacumat Basic ensures automatic topping-up of the system after the top-up water has been degassed.
Compact, easy to use and reliable design. Fully assembled and ready to connect. Highly efficient degassing through vortex technology. Dry run protection. The menu of the control unit is available in 18 languages. Wall mounted. Floor standing optional with the Vacumat Basic Floor Console (17001).
Specifications | Vacumat Basic |
Nominal pressure [PN] | 10 |
Working pressure range [bar] | 0.8 - 3.0 |
Max. glycol | 30% |
System flow temperature [°C] | 3 - 120 |
Working temperature [°C] | 3 - 70 |
Ambient temperature [°C] | 3 - 45 |
Top-up temperature [°C] | 3 - 30 |
Pressure top-up water [bar] | 0.8 - 8.0 |
Max. top-up volume [l/h] | 180 |
Electrical requirements [V] | 1 ~ 230 V - 50/60 Hz |
Power supply [kW] | 0.68 |
IP rating | IP 54 |
Nominal current [A] | 3.4 |
Noise output [dB(A)] | ~64 (max.) |
Flamco has been involved in the development, production and sale of high-quality components for use in HVAC systems since 1956. It is part of the stocklisted Aalberts NV, instituted in 1975. Along with Comap, which helps manage water and energy through its thermal and sanitary products that increase comfort in buildings, the Aalberts hydronic flow control business unit was constituted. Stronger together, Flamco and Comap will continue to build mission critical technologies to manage heating and cooling humanly with better financial and environmental efficacy. From source to emitter we partner with our customers to engineer seamless energy efficient hydronic systems for their building requirements.
comap.aalberts-hfc.com | aalberts-hfc.com
Stay up-to-date. Subscribe to our newsletter.
I agree to the processing of my personal data. Aalberts hydronic flow control attaches importance to your privacy.